A curtain wall firestop closes the gap between a floor slab and a glass facade. That gap runs around every floor of a glazed building, and it is easy to overlook. Left open, it lets fire and hot gases travel from one floor to the next, a risk we cover in our article on the hidden highway. This guide explains how a curtain wall firestop works, which parts it needs, how it is tested in India and what consultants should check on drawings and on site. It is written for architects, facade consultants, fire consultants and contractors.

Key Takeaways

Why the Slab Edge Is a Weak Point in Glass Buildings

A curtain wall hangs in front of the structure. It is fixed to each floor slab with brackets, and a gap is left between the slab edge and the inside face of the facade. Engineers need that gap. It allows for tolerances, and it lets the facade move with wind and temperature over its life.

The problem is continuity. The gap follows every slab around the whole perimeter of the building. If it stays open, each floor is connected to the floors above and below by a narrow void. A fire on one floor can use that void as a route upwards. The floor slab may be built to resist fire for hours, yet the compartment is broken at its edge.

This is why a curtain wall firestop matters. It closes the joint so that the floor keeps working as a fire barrier right up to the facade. Real fires have shown the same pattern, as covered in lessons from real world perimeter barrier failures.

The chimney effect inside the void

Hot gases rise. In a narrow vertical void, they rise quickly, which is the same principle as the stack effect in tall buildings. Flames and smoke enter the slab edge gap and travel to the floor above. Occupants on that floor may not know a fire has started below them. A curtain wall firestop blocks this path at every level. It also slows the spread of heat, which gives occupants more time to evacuate and gives firefighters a contained fire to tackle.

Leapfrogging across the facade

Fire can also spread outside the building. Heat can break the glazing on the fire floor. Flames then leave through the opening and lap up the outside of the facade towards the floor above. This is often called leapfrogging. The area in front of the slab, known as the spandrel zone, takes the heat first. Protecting it is part of complete curtain wall fire stopping, as the next sections explain.

Infographic showing how fire spreads at an unprotected slab edge and why a curtain wall firestop is needed

What a Curtain Wall Firestop Is Made Of

A curtain wall firestop is an engineered perimeter fire barrier. It is installed in the joint where a fire rated floor meets an exterior curtain wall. Its insulation, safing material, seals, mechanical attachments and the surrounding facade construction all work together. Performance comes from that combination, not from one product on its own.

This point changes how teams should specify. A product name and a time period in a schedule are not enough. The specification needs to describe the assembly: the joint width, the facade sections, the spandrel build up and the supports. FiroBlock describes this as system performance that belongs to the assembly. The same principle applies to any system you consider, including the one on our FS, MP and SP product page.

Slab edge firestop (FIROBLOCK FS)

The slab edge firestop is the core of the system. FIROBLOCK FS seals gaps of up to 150 mm between the floor slab and the facade within the specified system detail. It uses a non combustible mineral wool core with aluminium foil facings on both sides. The approved installation uses B235 support brackets and ATP 120 aluminium tape for support and joint continuity.

Mullion protection (FIROBLOCK MP)

Mullions are the vertical members of the curtain wall frame. In a fire, aluminium framing softens at temperatures far below its melting point. If it deforms, gaps can open at the slab edge. FIROBLOCK MP is a foil faced mineral wool insulation board that protects the mullions where the tested system requires it. FiroBlock publishes its nominal density as 160 kg/m³.

Spandrel protection (FIROBLOCK SP)

The spandrel is the opaque part of the facade between floors. FIROBLOCK SP is a dense mineral wool slab applied to a single backpan in this zone. Its foil faced surface provides thermal insulation and reflects radiant heat. It supports the fire performance of the spandrel construction and helps limit leapfrogging.

FS, MP and SP are used together according to the tested system documentation. They should not be described as three separately rated products. The rating applies to the complete curtain wall firestop assembly.

Infographic of the FS, MP and SP components of a curtain wall firestop perimeter fire barrier

Wet and dry curtain wall fire stopping compared

There are two broad approaches to curtain wall fire stopping. Each needs supporting test evidence for the actual condition.

A wet system relies on sealants or spray applied materials over a backing. These materials need curing time and suitable site conditions, such as clean, dry surfaces and the right temperature. Their performance depends heavily on the thickness and continuity achieved by the applicator.

A dry curtain wall firestop system uses preformed mineral wool components and mechanical supports. It can be installed without waiting for materials to cure, and it is tolerant of facade movement when installed under the right compression. FiroBlock uses this approach for its FS, MP and SP system.

Neither approach is correct for every project. The question is whether the chosen system has been tested in a configuration that matches the proposed facade. A firestop sealant on its own is usually not sufficient for a curtain wall gap. The barrier must perform as a complete assembly, including the spandrel and the supports.

Factor Wet approach Dry curtain wall firestop system
Main materials Sealant or spray over backing Preformed mineral wool with supports and tape
Curing Needs curing time No curing step
Site sensitivity Surface condition and weather matter Less sensitive to weather once installed
Movement Depends on sealant movement capability Relies on correct compression of the mineral wool
Evidence needed Test evidence for the full assembly Test evidence for the full assembly

Whichever approach you choose, record the tested system reference in the specification. Then check that the products delivered to site match that reference. Substitutions made late in a project are a common source of failures.

How Perimeter Fire Barriers Are Tested in India

Testing is what turns a set of materials into a system you can specify with confidence. Two standards are most relevant for a curtain wall firestop used in India.

IS 18190:2023

The Bureau of Indian Standards published IS 18190:2023, Fire Resistance of Perimeter Fire Barrier Joint System, Method of Tests. It is an Indian test method for perimeter fire barrier joint systems. The supporting evidence applies to the complete system rather than to an individual material. It gives Indian projects a local reference for this specific joint.

ASTM E2307

ASTM E2307 is a test method that evaluates a perimeter barrier’s ability to maintain a seal and resist fire at the junction between a floor and an exterior wall assembly. It uses an intermediate scale, multi storey test apparatus. The exterior wall in the test is part of the assembly, which is why the facade detail matters so much.

F rating and T rating

Two ratings are commonly reported. The F rating is the period for which the barrier resists the passage of flames and hot gases under the test criteria. The T rating also considers temperature rise on the unexposed side. FiroBlock reports that its tested FS, MP and SP assembly provides up to 120 minutes of fire resistance, with integrity and insulation performance demonstrated in the tested configuration, and that the curtain wall firestop system is tested to IS 18190 and ASTM E2307.

Two cautions apply. First, a rating cannot be moved automatically to a different facade, gap, substrate or installation detail. A higher rating, such as four hours, needs explicit test evidence or an approved assessment for that configuration. Second, ASTM E2307 does not quantitatively measure smoke leakage. A smoke leakage claim needs separate test evidence.

When you review a submittal, read the test report itself, not only a summary sheet. Check the joint width tested, the type of curtain wall, the spandrel materials, the support method and the duration achieved. Then compare each item with your drawings. Where they differ, ask whether the supplier holds an assessment that covers the change. This simple habit turns a rating on paper into evidence that genuinely fits your building, and it gives the fire consultant a clear basis for approval.

Designing a Curtain Wall Firestop Into the Facade

The best time to design a curtain wall firestop is while the facade and fire strategy are still being developed. Late decisions usually mean compromises on site.

Start with the joint. Confirm the slab edge gap, its tolerance and how much it will move. Movement comes from wind, temperature and building deflection. The perimeter barrier must stay effective within the movement covered by its supporting evidence. Permitted compression, extension, deflection and joint dimensions should be confirmed during specification.

Next, look at the facade components. The mullions, transoms, spandrel construction, backpan, insulation and anchors all affect compatibility. FiroBlock states that its system may be used in unitised or stick built curtain walls when the proposed detail is covered by applicable test evidence or a qualified project specific assessment accepted for the project.

Then coordinate the sequence. The firestop is installed after the facade is fixed but before ceilings and finishes close the area. Access, scaffolding and the order of trades should be planned together. Early coordination helps align the system with slab tolerances, mullions, transoms, backpans, spandrels and the construction sequence.

Infographic of the steps to specify, install and inspect a curtain wall firestop

Finally, share the information the supplier needs. FiroBlock asks for project location, available drawings, slab edge dimensions, required fire rating and the proposed schedule. With these, its technical team can review the application and recommend a configuration. Learn more about this approach on our about page.

Build a short curtain wall fire stopping checklist into your design reviews. Is the joint width within the range of the tested detail? Is the spandrel build up similar to the tested one? Are the mullion and transom positions compatible? Is there space to fix the support brackets? Each yes reduces risk on site. Each no is a prompt to ask the supplier for guidance before tender.

Do not forget the corners and junctions in your curtain wall fire stopping. Internal and external corners, column positions, changes in slab level and the meeting point with solid walls all interrupt a simple straight run. These locations need their own details on the drawings. A curtain wall firestop that is continuous along straight runs but missing at corners leaves the same gap you were trying to close.

Where a Curtain Wall Firestop Is Needed

Any building with a curtain wall or glazed facade has a slab edge joint on every floor. That joint needs a tested perimeter barrier, whatever the building is used for. The building type changes the priorities, not the need.

Commercial offices and IT parks

Office towers and IT parks often use full height glazing on large floor plates. They can have long, continuous slab edges and many floors connected by the same facade. A curtain wall firestop here protects open plan floors that may hold hundreds of people. Coordination with raised floors and ceiling voids is common.

Hospitals and healthcare buildings

Patients may not be able to leave quickly. The fire strategy in a hospital often relies on moving people horizontally to a safe compartment on the same floor. That only works if the floors above and below stay separated. Reliable curtain wall fire stopping at the slab edge supports this approach.

Hotels, malls and mixed use towers

Hotels have sleeping occupants. Malls have large crowds and big glazed frontages. Mixed use towers combine retail, offices and apartments, each with different hours and occupants. In all of these, a curtain wall firestop helps contain a fire to the floor where it starts. FiroBlock lists commercial towers, IT parks, hospitals, airports, malls, hotels and high rise residential projects among the applications for its system.

Retrofit projects need the same care with curtain wall fire stopping. When an older facade is replaced or reclad, the slab edge joint is often exposed. That is the right moment to check whether a tested curtain wall firestop is present and to install one if it is not.

Common Curtain Wall Firestop Mistakes on Site

Most curtain wall fire stopping failures are not caused by poor products. They come from small changes and gaps in coordination. Watch for these.

Each of these breaks the link between the installed work and the test evidence. The fix is simple but needs discipline. Name the tested system in the specification, check deliveries against it and inspect every floor before it is closed up.

Late design changes deserve special attention. A change to the slab edge, the facade bracket or the spandrel build up can change the joint. When that happens, ask the supplier to confirm that the curtain wall firestop detail still matches the evidence, or that a project specific assessment covers the new condition.

Maintenance teams also play a part after handover. Cables and pipes are sometimes routed near the facade during fit outs. If a contractor removes part of the perimeter fire barrier, it must be reinstated to the same detail. Clear labels and handover records make this easier and keep the curtain wall firestop intact for the life of the building.

Installation, Inspection and Handover

A curtain wall firestop that is correctly designed can still fail if it is installed badly. Installation quality deserves the same attention as design in curtain wall fire stopping.

The system should be installed by trained personnel working to approved drawings and the manufacturer’s instructions. Changes to materials, dimensions, compression or attachment methods need technical approval before they are made on site. This keeps the installed work consistent with the tested assembly.

Inspection of the perimeter fire barrier should verify a short list of items on every floor:

Photographs and location based records should be kept for inspection and handover. They give the fire consultant and the building owner evidence of what was installed and where. They also help facility teams protect the perimeter fire barrier during later fit outs, when ceilings and facades are sometimes opened.

FiroBlock provides technical review, system selection, installation support, inspection and project documentation, with the scope agreed for each project. Ask your supplier what its handover pack contains before you appoint it.

Choosing a Curtain Wall Firestop Supplier

A good curtain wall fire stopping supplier helps you match the right tested system to your facade. Use the questions below when you compare options.

Also ask how the supplier treats differences between your facade and the tested one. A responsible supplier will explain when a project specific assessment is needed instead of assuming the rating transfers.

Local manufacture can help with lead times and site support. FiroBlock systems are made in India, which means project teams can discuss drawings, mock ups and delivery schedules with a team close to their sites. Whatever the source, the deciding factor should always be test evidence that matches your facade, backed by people who can support installation and inspection.

Fire safety does not stop at the facade. Large openings inside a building, such as atriums and lift lobbies, need their own protection. FiroBlock also supplies automatic fire curtains for these openings, which are tested separately to BS EN 1634 1, as the curtain product page sets out. The two systems solve different problems and their test evidence should never be mixed. You can see both ranges on our products page.

For more on those larger openings, read our practical guide to these systems.

Conclusion

A curtain wall firestop keeps the floor slab working as a fire barrier right up to the facade. It closes the slab edge gap, protects mullions and spandrels, and limits both the chimney effect and leapfrogging. Its rating belongs to the tested assembly, so match the facade to the evidence, install to approved details and keep clear records. FiroBlock’s FS, MP and SP system is tested to IS 18190 and ASTM E2307. Share your facade drawings and talk to our technical team about your project.

Frequently Asked Questions

What is a curtain wall firestop?

It is a perimeter fire barrier installed in the gap between a floor slab and a curtain wall facade. It restricts the passage of flames and hot gases through that gap and helps keep each floor working as a separate fire compartment.

Why is there a gap between the slab and the curtain wall?

The gap allows for construction tolerances and for movement of the facade caused by wind, temperature and building deflection. It is needed for the facade, but it must be closed with a tested perimeter fire barrier.

Is firestop sealant enough for a curtain wall gap?

Usually not. A curtain wall gap needs a complete assembly of insulation, supports, seals and facade components that has been tested together. A sealant used alone rarely matches the tested configuration of a perimeter barrier.

What does IS 18190 cover?

IS 18190:2023 is the Bureau of Indian Standards method of tests for the fire resistance of perimeter fire barrier joint systems. It assesses the complete joint system rather than an individual material used within it.

What is the difference between F rating and T rating?

The F rating is how long the barrier resists the passage of flames and hot gases. The T rating also considers temperature rise on the unexposed side. Both apply only to the tested configuration.

Can a two hour rating be used on any facade?

No. Ratings cannot be transferred automatically between different facades, gaps, substrates or installation details. Check that the test evidence or an approved project assessment covers your specific facade and joint before relying on any rating.

Does a curtain wall firestop stop smoke?

Fire resistance and smoke leakage are assessed separately. ASTM E2307 does not quantitatively measure smoke leakage, so any smoke leakage claim needs its own test evidence for the system and the intended application.

Who should install a perimeter fire barrier?

Trained installers working to approved drawings and the manufacturer’s instructions. Any change to materials, dimensions, compression or attachments should be approved technically before it is made on site, then recorded in the handover file.

How does a firestop relate to other passive fire protection?

It is one part of a wider passive fire protection strategy that also includes fire rated floors, walls, doors and opening protection. Read what fire curtains do for one example of opening protection.