A curtain wall firestop detail is where design intent meets site reality. It shows how the barrier fits into the gap between the floor slab and the facade, and how it is supported. If the detail is vague, installers fill the gaps with guesses. This guide explains what a good detail must show, how to read the slab edge joint, how mullions and spandrels affect it and which changes need approval. Use it when you review facade and fire stopping drawings. For the wider system, start with our complete guide to slab edge protection.

Key Takeaways

What a Curtain Wall Firestop Detail Must Show

A detail is not a product label on a section. It is an instruction for installers and a record for inspectors, so it needs enough information to build and check the work.

At minimum, a curtain wall firestop detail should show the slab edge, the inside face of the facade and the gap between them. It should name the tested system it is based on. It should show the barrier material, its depth and the direction it is fitted. It should show the supports, the seals and how joint continuity is achieved along the run.

It should also show the facade parts that form part of the assembly. These include the mullions and transoms near the slab, the spandrel panel and its backpan, and any insulation behind the spandrel. A curtain wall firestop performs as a complete assembly, so leaving these out of the drawing hides half of the system.

Finally, the detail should carry notes. Typical notes cover the required fire rating, the permitted joint width and movement, installation by trained personnel and the rule that changes need technical approval. Our FS, MP and SP product page sets out the system parts to include.

Infographic listing what a curtain wall firestop detail must show on slab edge drawings

Reading the Slab Edge Joint

The joint is the heart of every slab edge firestopping detail. Its width, tolerance and movement decide whether the barrier will stay tight in a fire.

Start with the nominal joint width. FiroBlock states that FIROBLOCK FS seals gaps of up to 150 mm between floor slabs and curtain wall facades within the specified system detail, and its product summary describes voids from 20 to 150 mm. Check that the gap on your drawings falls within the range covered by the evidence.

Then check tolerance. Slab edges are rarely perfectly straight. A gap drawn as 100 mm may vary along the building. The slab edge firestopping detail should say how the barrier deals with this variation, and what happens if the gap on site is outside the permitted range.

Next, look at compression. Mineral wool barriers rely on being fitted under compression so they stay in contact with the slab and the facade. FiroBlock notes that joint dimensions, compression and facade movement must be addressed in the installation design. A curtain wall firestop detail that does not mention compression leaves the most important site check undefined.

Finally, check support and continuity. The approved FiroBlock installation uses B235 support brackets and ATP 120 aluminium tape for support and joint continuity. Your detail should show where brackets go, at what spacing, and how joints between lengths are sealed.

Mullions, Transoms and the Spandrel

The facade around the joint is part of the system. A good curtain wall slab edge firestop detail shows these parts clearly and matches them to the tested assembly.

Mullion positions matter because the barrier must fit tightly around them. FIROBLOCK MP is a mineral wool board that protects vertical mullions where the tested system requires it. The detail should show which mullions are protected and how the board is fixed. Transom heights matter too, because a transom close to the slab changes the space available for the barrier.

The spandrel needs its own attention. FIROBLOCK SP is a dense mineral wool slab applied to a single backpan in the spandrel zone. The detail should show the backpan, the SP slab and how it meets the curtain wall slab edge firestop. If your facade uses a different spandrel build up, such as a double backpan or a different insulation, flag it for review.

Compatibility depends on the mullions, transoms, spandrel construction, backpan, insulation, anchors and slab edge included in the tested or assessed assembly. FiroBlock’s technical team reviews the facade drawings, slab edge joint and supporting components before confirming suitability for unitised or stick built facades. You can ask for this review early.

Infographic of the steps to review a slab edge firestopping detail for a curtain wall

Notes, Schedules and Mock Ups

Drawings alone rarely carry every instruction. Notes, schedules and a site mock up make the curtain wall firestop detail easier to build correctly.

Add a schedule that lists each facade type on the building with its joint width, fire rating and detail reference. Large projects often have several curtain wall types, and each may need a different arrangement. A schedule stops installers from applying one curtain wall firestop detail everywhere by default.

Write the notes on every slab edge firestopping detail in plain language. State the tested system, the permitted joint range, the compression required, the support spacing and the inspection points. Add a note that any deviation must be reported before work continues. Short, clear notes are read on site. Long notes copied from a brochure are not.

Then build a mock up of the curtain wall firestop detail. Install a short length of the barrier at a typical slab edge, including a mullion and the spandrel. Let the facade contractor, the firestop installer and the consultant inspect it together. Agree on the finished standard and photograph it. The mock up becomes the reference for every floor that follows, and it often reveals clashes the drawings missed.

Corners, Junctions and Changes on Site

Straight runs are easy to draw. The risks sit at corners, junctions and late changes, so each one needs its own curtain wall firestop detail.

Give internal and external corners a separate slab edge firestopping detail. Show how the barrier turns the corner without a gap, and how supports are arranged there. Do the same for columns that meet the facade, changes in slab level, steps in the facade line and the end of a curtain wall where it meets a solid wall or another cladding system.

Service penetrations near the facade need care too. A cable tray or pipe passing close to the slab edge can interrupt the barrier. These firestop conditions often need a different tested system, so coordinate them early.

Late changes are the biggest risk. FiroBlock states that changes to materials, dimensions, compression or attachment methods require technical approval. If the slab edge moves, the bracket changes or the spandrel build up is revised, update the curtain wall firestop detail and confirm it still matches the evidence before installation begins.

On site, inspection should verify the tested system reference, gap dimensions, insulation depth and compression, seal continuity, attachments and the spandrel and mullion details. Keep photographs and location based records for handover, as explained in our article on why curtain wall gaps must be sealed.

Treat the as built record as part of the curtain wall firestop detail. Mark any approved changes on the drawings, attach the inspection photographs and file them with the test report. Facility teams can then repair the barrier to the same standard if a later fit out disturbs it.

Conclusion

A curtain wall firestop detail turns a tested system into instructions that installers can follow and inspectors can check. It must show the joint width, compression, supports, mullion protection and spandrel build up, and it must cover corners and junctions. Any change needs technical approval before work starts. FiroBlock reviews facade drawings, slab edge joints and supporting components before confirming a configuration. Learn how we support project teams from design to handover on our about page.

Frequently Asked Questions

What is a curtain wall firestop detail?

It is a drawing that shows how a perimeter fire barrier fits into the gap between the floor slab and the facade. It includes the barrier, supports, seals, mullion protection and spandrel build up of the tested system.

What joint width can a slab edge firestop seal?

It depends on the tested system. FiroBlock states that FIROBLOCK FS seals gaps of up to 150 mm within the specified system detail. Always check the range covered by the evidence for your project.

Why does compression matter in a slab edge firestopping detail?

Mineral wool barriers rely on compression to stay in contact with the slab and facade. Without the right compression, gaps can open as the facade moves or as heat affects the frame during a fire.

Do mullions need fire protection?

Where the tested system requires it, yes. Aluminium mullions can lose strength when heated and deform. Mullion protection boards limit heat exposure and help keep the slab edge joint closed during a fire.

What is a spandrel backpan?

It is the panel behind the opaque spandrel zone of a curtain wall. In FiroBlock’s system, the SP mineral wool slab is applied to a single backpan. Different backpan arrangements should be reviewed against the evidence.

Should corners have separate details?

Yes. Internal and external corners, columns, slab level changes and junctions with other cladding interrupt straight runs. Each needs its own detail showing how the barrier stays continuous and how it is supported.

Can installers change materials on site?

Not without technical approval. Changes to materials, dimensions, compression or attachment methods can affect performance. Any change should be reviewed, approved and recorded before it is installed on site, and the drawings updated.

Does the curtain wall firestop detail differ for unitised and stick built facades?

It can. The slab edge condition and the position of mullions and transoms vary between systems. Suitability depends on test evidence or an accepted project specific assessment for the actual facade and its slab edge.

Where can I see the FiroBlock product range?

Visit the FiroBlock products page to see the curtain wall firestop system and automatic fire curtains, with the test references that apply to each product and its tested configurations for commercial projects across India.

How does this fit into a wider fire strategy?

The slab edge barrier is one part of compartmentation. Read lessons from real world fires to see what happens when floors, facades and openings fail to keep a fire contained.