Spandrel protection against leapfrog fire spread is one of the least visible parts of a glazed facade. It sits behind the opaque bands between floors, where nobody sees it once the building is finished. Yet this zone takes the heat when flames leave a window and climb the outside of a building. This guide explains what the spandrel zone is, how leapfrogging happens and how spandrel and mullion fire protection work with the slab edge firestop. For the wider system, start with our complete guide to slab edge protection.
Key Takeaways
- Spandrel protection against leapfrog fire spread limits heat transfer through the opaque zone in front of each floor slab, which slows leapfrogging.
- Mullion protection keeps aluminium framing from deforming and opening gaps at the slab edge during a fire.
- Spandrel and mullion fire protection only perform as part of a complete tested slab edge assembly.
What the Spandrel Zone Is
The spandrel is the opaque part of a curtain wall in front of each floor slab. It hides the slab edge, the brackets and the services, and it is where fire meets the facade first.
On a curtain wall building, the vision glass shows the view. Between one floor’s windows and the next, there is a band that hides the floor structure. This band is the spandrel zone. It usually consists of opaque glass, metal backpans, insulation or other non vision materials.
Because it sits directly in front of the slab, the spandrel zone covers the joint where the floor meets the facade. That makes it a critical place for fire. If the spandrel fails, flames can reach the floor above even when the slab edge gap itself is sealed. Spandrel protection deals with this risk from the outside face of the joint.
Spandrel design also varies widely between projects. Some use a single backpan with insulation. Others use shadow boxes, double backpans or stone cladding. Each build up behaves differently in a fire, which is why spandrel protection must be matched to the tested arrangement.
Architects choose spandrel finishes for appearance, thermal performance and cost. Fire performance should sit on that list from the start. When the spandrel build up is fixed early, the facade contractor and the firestop supplier can confirm spandrel protection before the design is frozen, instead of reworking panels later. That early check costs little and avoids redesign when the facade package is already on site.
How Leapfrogging Happens
Leapfrogging is fire spread up the outside of a building. It bypasses the floor slab entirely by travelling across the facade from one floor to the next.
It starts inside. A fire grows in a room until the heat breaks the vision glass. Flames then leave through the opening and lap upwards against the facade. They heat the spandrel zone above. If the spandrel or the glass on the next floor fails, the fire re enters the building one level higher. The process can then repeat.
Leapfrogging is fast because the facade offers a continuous path. Each floor exposes the next one above it. The taller the building and the larger the glazed area, the more floors are at risk. Internal measures such as sprinklers help control the fire inside, but the facade route still needs passive protection at every level. Spandrel protection is that protection on the outside face of the joint.

This leapfrogging pattern has been seen in real high rise fires. NIST’s overview of the 1988 First Interstate Bank fire in Los Angeles is a widely studied example of vertical fire spread in an office tower. Fire investigators still use it to explain how quickly a fire can climb a building. Our article on lessons from real world fires looks at this and other cases. Spandrel protection aims to slow this process so that the fire stays on its floor for longer.
How Spandrel Protection Works
Spandrel protection uses insulation in the spandrel zone to limit heat transfer and reflect radiant heat. It supports the facade’s fire performance at the most exposed point.
FIROBLOCK SP is designed for this zone. It is a dense, non combustible mineral wool slab with an aluminium foil facing. It is applied to a single backpan in the spandrel area. Its insulation limits heat transfer, while its foil faced surface reflects radiant heat. Together, these help reduce the risk of fire propagation through the spandrel.
Spandrel protection does not work alone. FiroBlock states that SP has been tested together with FIROBLOCK FS for the slab edge and FIROBLOCK MP for the mullions. In that integrated test, the assembly demonstrated up to two hours of fire resistance. The result belongs to the combined system, not to SP as a separate product.
Installation quality matters as much as the material. The slab must cover the backpan without gaps and stay fixed in place. Joints between slabs should be tight. Where the spandrel meets the slab edge firestop, the two parts should connect as the tested detail shows. Small gaps can let heat bypass the insulation and weaken spandrel protection where it is needed most.
This is why a specification should never list spandrel insulation as a standalone item. It should reference the complete tested assembly, as described on our FS, MP and SP product page.
Why Mullion Protection Matters
Mullions are the vertical members of the facade frame. In a fire, protecting them helps keep the frame and the slab edge joint in shape.
Most curtain wall frames are aluminium. Aluminium loses strength at temperatures far below its melting point. If a mullion near the slab edge softens and bends, the facade can move away from the barrier. A gap opens, and the joint stops working as a seal.
FIROBLOCK MP is a high density mineral wool board with a nominal density of 160 kg/m³. It insulates aluminium mullions and transoms exposed to high temperatures. By limiting heat exposure, it helps prevent deformation that could compromise the mullions or the connected spandrel assembly. FiroBlock notes that MP is tested as part of a complete facade assembly.
Transoms near the slab need the same thought. A horizontal member close to the floor changes the space for the barrier and the way heat reaches the frame. Check transom heights against the tested detail. Where they differ, ask whether the mullion protection and the slab edge firestop still match the evidence for your facade.

Designing Spandrel and Mullion Fire Protection Together
The slab edge firestop, the mullion protection and the spandrel protection form one system. Design and inspect them together.
Start from the facade drawings. Mark the spandrel build up, the backpan, the mullion spacing and the transom positions. Compare them with the tested assembly. If your spandrel uses a different backpan arrangement or insulation, raise it with the supplier before tender. A project specific assessment may be needed.
On site, check that SP slabs cover the backpan fully and that MP boards are fixed to every mullion the tested detail requires. These parts are hidden once the facade is closed, so inspect and photograph them floor by floor. Our technical team can review your facade details and confirm the right configuration.
Keep the records with the test report. Photographs of SP and MP before the facade is closed are often the clearest proof that spandrel protection was installed as designed. They help the fire consultant at handover and help facility teams if the facade is ever opened for repairs.
Conclusion
Spandrel protection against leapfrog fire spread works at the most exposed point of a glazed facade. It limits heat transfer through the spandrel, while mullion protection keeps the aluminium frame from deforming. Both perform only as part of a tested assembly with the slab edge firestop, so match your facade to the evidence and inspect hidden parts before they are closed. Explore the FS, MP and SP system and contact FiroBlock to discuss your facade.
Frequently Asked Questions
What is the spandrel zone in a curtain wall?
It is the opaque band of the facade in front of each floor slab. It usually includes opaque glass, metal backpans and insulation, and it hides the slab edge, brackets and services behind it.
What is leapfrog fire spread?
It is fire spread up the outside of a building. Flames leave a broken window, climb the facade and re enter the floor above, bypassing the fire rated floor slab between the two levels entirely.
How does spandrel protection against leapfrog fire spread work?
It places dense mineral wool insulation in the spandrel zone. The insulation limits heat transfer and a foil facing reflects radiant heat, which helps slow fire propagation through this exposed part of the facade.
Is spandrel insulation enough on its own?
No. Spandrel protection should be part of a complete tested assembly that includes the slab edge firestop and mullion protection. Ratings belong to the combined tested system, not to one component used on its own.
Why do aluminium mullions need protection?
Aluminium loses strength at temperatures well below its melting point. If a mullion near the slab edge bends, gaps can open in the perimeter barrier. Mullion protection limits heat exposure to reduce that risk.
What fire resistance has the FiroBlock assembly shown?
FiroBlock states that SP, tested together with FS and MP, demonstrated up to two hours of fire resistance as an integrated curtain wall assembly. The result applies to that tested configuration only, not to other facades.
Does every facade need spandrel protection?
It depends on the facade design and the tested system chosen. Where the tested assembly includes spandrel protection, it should be installed as detailed. Review your spandrel build up with the supplier early.
Can a different spandrel build up use the same rating?
Not automatically. Shadow boxes, double backpans or different insulation can change performance. Ask whether test evidence or a qualified project specific assessment covers your actual spandrel arrangement before you rely on any rating.
Who is FiroBlock?
FiroBlock is an Indian passive fire protection brand offering curtain wall firestop systems and automatic fire curtains. Learn about FiroBlock and how its technical team supports projects from early drawing review through to final handover.
Where does facade protection fit in passive fire protection?
Facade protection is one layer of passive fire protection, alongside fire rated floors, walls and doors. Read why curtain wall gaps must be sealed for the wider context and overall strategy.